2024.10.04 Recall: SIBA NH Fuse-Links of size NH000
04 October 2024
The following notice has been issued by the Office for Product Safety and Standards.
Product
SIBA NH Fuse-Links of size NH000
Type
Electrical fuse link
Brand
SIBA
Product description
Metal electrical fuse link. Manufacture date March 2024 - July 2024. Affected fuses can be identified by the production period, either by the calendar weeks on the label on the packaging (032024 to 112024) and/or the quarterly imprint on the fuse: 124 = quarter 1 / 2024.
Affected units
20-000-13/35E1 - Purchased from April 2024 - Batch code 00413667; 20-000-13/50A - Purchased from May 2024 - Batch code 00523660; 20-000-13/63A - Purchased from June - July 2024 - Batch code 00516957; 20-477-08/50A - Purchased from July 2024 - Batch code 00441310
Hazard
The product has been identified by the manufacturer as presenting a risk of as the sand sealing cap may not seal correctly, which could cause the sand to leak during use in high-vibration environments. This can negatively influence the extinguishing behaviour of the fuse in the event of a short circuit.
The product does not meet the requirements of the General Product Safety Regulations (2005).
Corrective action
The product has been recalled from end users by the manufacturer. Owners should stop using the product immediately and contact Europa's customer service team to arrange for a return to be made.
Europa can be contacted at:
- Telephone: 01582 692 448
- Email: [email protected]
© 2025 itsa Ltd.