2024.10.23 Recall: Xtralis and System Sensor OSID-R Conventional Detector

23 October 2024

The following notice has been issued by the Office for Product Safety and Standards.

Product
Xtralis and System Sensor OSID-R Conventional Detector

Type   
Construction Products - OSID-R Conventional Detector

Brand
Xtralis and System Sensor

Country of Origin      
Mexico

Product Description  
An Open area Smoke Imaging Detection Unit (OSID) for protecting large, open areas. The above images show the labelling found on the right side of the unit after removing the cover.

Detector

Models           
OSI-RE and OSI-RE-SS

Affected batches       
Between 1041 (included) and 3043 (included) (Please note that there are 57 affected units, all of which are traceable)

Hazard
It has been identified that a small number of affected detectors have failed and did not notify the fire panel of their failure. This may result in a fire being undetected, which may lead to users being trapped in a fire or receiving burns.

The affected detectors do not meet the requirements of the Construction Products Regulations 2013.

Corrective action
The affected products have been recalled from end users.

All 57 affected detectors are traceable through installers / customers and can be identified by a combination of the models and the production date codes.